Skip to product information
1 of 1

Moxa

MOXA MGATE 5118 INDUSTRIAL ETHERNET GATEWAYS

MOXA MGATE 5118 INDUSTRIAL ETHERNET GATEWAYS

Regular price $836.00 CAD
Regular price Sale price $836.00 CAD
Sale Sold out

Features and Benefits

  • CAN-J1939 to Modbus/PROFINET/EtherNet/IP gateway
  • 2 x 10/100Mbps T(x) ports and 1 x RS-232/422/485 port
  • 12 to 48 VDC input power
  • Metal body
  • 0 to 60°C operating temperature
View full details

Description

The MGate 5118 industrial protocol gateways support the SAE J1939 protocol, which is based on the CAN bus (Controller Area Network). SAE J1939 is used to implement communication and diagnostics among vehicle components, diesel engine generators, and compression engines, and is suitable for the heavy-duty truck industry and backup power systems. It is now common to use an engine control unit (ECU) to control these kinds of devices, and more and more applications are using PLCs for process automation to monitor the status of J1939 devices connected behind the ECU.

The MGate 5118 gateways support the Modbus RTU/ASCII/TCP, EtherNet/IP, and PROFINET protocols to support most PLC applications. Devices that support the J1939 protocol can be monitored and controlled by PLCs and SCADA systems that use the Modbus RTU/ASCII/TCP, EtherNet/IP, and PROFINET protocols. With the MGate 5118, you can use the same gateway in a variety of PLC environments.

Specification

Number of Ports: 2 (1 IP address, supports Ethernet cascading)
Speed: 10/100 Mbps, Auto MDI/MDIX
Connector: 8-pin RJ45
Magnetic Isolation Protection: 1.5 kV (built-in)
Protocols: Modbus TCP (Client/Server), PROFINET (I/O device), EtherNet/IP (Scanner/Adapter)
RS-232 Signals: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Signals: Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Signals: Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Signals: Data+, Data-, GND
Protocols: SAE J1939, Modbus RTU/ASCII/TCP, PROFINET, EtherNet/IP
Protocol Conversion: J1939 to Modbus RTU/ASCII (Master/Slave), J1939 to Modbus TCP (Client/Server), J1939 to EtherNet/IP (Scanner/Adapter), J1939 to PROFINET (I/O Device)
Protocols: SAE J1939
Number of Ports: 1
Connectors: 6-pin terminal block
Terminator: 120 Ω
Isolation: 2 kV (built-in)
Data Rate: 250 kbps and 500 kbps
Data Bits: 8
Stop Bits: 1, 2
Parity: Even, Odd, Space, Mark, None
Flow Control: RTS/CTS, RTS Toggle
Baudrate: 50 bps to 921.6 kbps
Configuration Options: Web console
Utility: Device Search Utility (DSU) for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1/10 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2
Support: MXview, MXconfig, IEC 62443-4-2
Network Protocols: TCP/IP, UDP, HTTP, SMTP, NTP, DNS, DHCP Client, SNMP (v1, v2, v3), MIB-II, ARP, Telnet
Protocols: Modbus RTU/ASCII (Master/Slave)
Number of Ports: 1
Serial Standards: RS-232/422/485, software selectable
Connectors: DB9 male
Pull High/Low Resistor for RS-485: 1 kΩ, 150 kΩ
Terminator for RS-485: 120 Ω
Isolation: 2 kV (built-in)
MTBF: 727,873 hrs
Input Current: 416 mA @ 12 VDC, 195 mA @ 24 VDC; 110 mA @ 48 VDC
Input Voltage: 12 to 48 VDC
Power Connector: Terminal block
Dimensions: 45.8 x 105 x 134 mm (1.8 x 4.13 x 5.28 in)
Housing: Metal, IP30
Operating Temperature: -0 to 60°C (32 to 140°F)
Weight: 589 g (1.30 lb)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Vibration: IEC 60068-2-6, IEC 60068-2-64
Shock: IEC 60068-2-27
Drop: IEC 60068-2-32
Safety: EN 60950-1(LVD), UL 61010-2-201
Hazardous Location: Class I Division 2, ATEX, IECEx
EMC: EN 61000-6-2/6-4
EMI: CISPR 22, FCC Part 15B Class B
EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV, IEC 61000-4-5 Surge: Power 1 kV; Signal: 1 kV, IEC 61000-4-6 CS: 10 V, IEC 61000-4-8 PFMF: 10 A/m
Storage Card Slot: 1 microSD (SDHC) card slot; supports up to 32 GB